| SYMPTOM: |
CORRECTIVE ACTION: |
| Lamps will not operate. |
1. Check if there is power to the fixture. |
| 2. Be sure lamp is properly seated in socket. |
| 3. Replace lamp. |
| 4. Reseat or change starter (preheat only). |
| 5. Check wiring connections. |
| 6. Test ballast. |
| Slow or erratic starting. |
1. Check ground (fixture must be grounded for reliable starting). |
| 2. Check ballast label for correct lamp. |
| 3. Check wiring connections. |
| 4. Check for low voltage supply. |
| 5. Be sure lamp is correctly seated in socket. |
| 6. Test Ballast. |
| Excessive noise. |
1. Tighten loose components. |
| 2. Install ballasts of the proper sound rating. |
| 3. Replace faulty ballast(s). Normal operation should resume. |
| 4. Note: All fluorescent ballasts emit some noise. |
| Lamp(s) are cycling. |
1. Check air temperature in and around fixture. |
| 2. Check ballast and coil temperature - ballast case temperatures should not exceed 90C and coil temperatures should not exceed 105C. |
| 3. Remove building insulation from above fixtures to allow heat dissipation. |
| 4. Replace faulty ballast(s). Normal operation should resume. |
| Interferance. |
1. Radio and antenna must be 4- 10 feet from lamps. |
| 2. Correct condition by use of radio interferance filters. |
| 3. Lighting fixtures should be on separate electrical circuits. |